Date Inspected | Location in School | Health & Safety Issue Observed | Class | Action Taken By | Date Action Taken | Details |
09/27/21 | 205 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Principal | 10/01/21 | Details |
09/27/21 | Science Lab | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 10/01/21 | Details |
10/20/21 | 26 | ceiling damaged (specify) | A | Caretaker | 12/01/21 | Details |
10/20/21 | boiler room | eyewash station required or in need of repair (specify) | A | Caretaker | 12/01/21 | Details |
10/20/21 | Old Boiler Rom | leaking/pooling/ponding of liquid (specify liquid and source if possible) | A | Caretaker | 10/29/21 | Details |
10/20/21 | 26 | extinguisher - tag missing or annual inspection more than 3 months overdue | A | Caretaker | 10/29/21 | Details |
10/20/21 | Mech Room 1st fl | eyewash station required or in need of repair (specify) | A | Caretaker | 12/01/21 | Details |
10/20/21 | Fan Room 1 | lighting in need of repair (maintenance issue) | A | Caretaker | 10/29/21 | Details |
10/20/21 | Prep room 302 | chemical storage areas are not clearly identified according TDSB Chemical Storage labelling guidelines. | B | Caretaker | 03/01/22 | Details |
10/20/21 | Prep room 302 | NO FOOD & DRINK Sticker - not present or not being observed | B | Caretaker | 03/01/22 | Details |
10/20/21 | Prep room 302 | broken glass container is required in science storage/prep room | B | Caretaker | 03/01/22 | Details |
10/20/21 | Prep room 302 | TDSB Chemical Storage poster not visible Science Prep Room | B | Caretaker | 03/01/22 | Details |
10/20/21 | Prep room 302 | waste containers are not available or properly labelled as required in Science Prep Room | B | Caretaker | 03/01/22 | Details |
11/04/21 | 227 | trip hazard (i.e. flooring, other materials) | A | Caretaker | 11/29/21 | Details |
11/04/21 | boiler room | leaking/pooling/ponding of water or liquid (be as specific as possible) | A | Caretaker | 11/29/21 | Details |
12/20/21 | Runnymede CI Health & Safety Bulletin Board | Workplace Inspection Report posted? | B | Principal | 02/01/22 | Details |
12/20/21 | Hall by main boiler room | lighting in need of repair (maintenance issue) | A | Principal | 02/01/22 | Details |
12/20/21 | hall by large gym | ceiling tiles missing/loose | A | Principal | 02/01/22 | Details |
12/20/21 | 224 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Principal | 02/01/22 | Details |
12/20/21 | 212 | ceiling tiles missing/loose | A | Principal | 02/01/22 | Details |
01/25/22 | Pool Fan Room | exposed wiring/damaged cord/ground pin missing | A | Principal | 02/01/22 | Details |
01/25/22 | Health & Safety Bulletin Boards. | Health & Safety bulletin board - required items are missing or outdated (be specific) | B | Principal | 02/01/22 | Details |
01/25/22 | pool filter room | insulation - required or in need of repair | A | Principal | 02/01/22 | Details |
01/25/22 | Mountainview Alternative | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Principal | 02/01/22 | Details |
01/25/22 | Fan Rm in main office | portable ladder - damaged or not securely stored | A | Principal | 02/01/22 | Details |
01/25/22 | boiler room | ventilation (specify) | A | Principal | 02/01/22 | Details |
02/28/22 | Main Boiler Room | equipment damaged or not secured (specify) | B | Principal | 03/01/22 | Details |
02/28/22 | Large Gym | panel (specify) | A | Principal | 03/01/22 | Details |
02/28/22 | Boys Changroom | equipment damaged or not secured (specify) | B | Principal | 03/01/22 | Details |
02/28/22 | Mech Room 1st fl | inappropriate storage of materials/furniture/shelving, or clutter | B | Principal | 03/01/22 | Details |
02/28/22 | Mech Room 1st fl | lighting is insufficient for task in work area, room number and why | B | Principal | 03/01/22 | Details |
02/28/22 | Mech Room 1st fl | panel (specify) | A | Principal | 03/01/22 | Details |
02/28/22 | Hall | emergency lighting damaged/missing | A | Principal | 03/01/22 | Details |
02/28/22 | Main Boiler Room | equipment damaged or not secured (specify) | B | Principal | 03/01/22 | Details |
02/28/22 | pool filter room | emergency lighting damaged/missing | A | Principal | 03/01/22 | Details |
02/28/22 | pool filter room | eyewash station required or in need of repair (specify) | A | Principal | 03/01/22 | Details |
02/28/22 | fan rm near caretaker rm | exposed wiring/damaged cord/ground pin missing | A | Principal | 03/01/22 | Details |
02/28/22 | Hall | emergency lighting damaged/missing | A | Principal | 03/01/22 | Details |
02/28/22 | Hall | emergency lighting damaged/missing | A | Principal | 03/01/22 | Details |
03/04/22 | Staff washroom beside library | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | | | Details |
03/04/22 | cafe kitchen | unable to inspect (specify why if possible) | B | | | Details |
03/04/22 | 15 | unable to inspect (specify why if possible) | B | | | Details |
03/04/22 | copy room in office area | extinguisher - tag missing or annual inspection more than 3 months overdue | A | | | Details |
03/04/22 | fan in copy room | inappropriate storage of materials/furniture/shelving, or clutter | B | | | Details |
03/04/22 | main office | Joint Health & Safety Committee meeting minutes - latest copy not posted | B | | | Details |
03/04/22 | physics office | portable ladder - damaged or not securely stored | A | | | Details |
03/04/22 | physics office | ceiling tiles missing/loose | A | | | Details |
03/04/22 | main office | Workplace Inspection Report posted? | B | | | Details |
04/06/22 | pool filter room | fire extinguisher not adequately charged or mounted | A | Principal | 06/01/22 | Details |
04/06/22 | boiler room | ACM - yellow asbestos bags present (incl. number of bags) | A1 | Principal | 06/01/22 | Details |
04/06/22 | pool filter room | egress blocked or insufficient path (doorway, hallway or stairwell) | B | Principal | 06/01/22 | Details |
04/06/22 | Fan Room 3 | fire extinguisher not adequately charged or mounted | A | Principal | 06/01/22 | Details |
04/06/22 | 22 | equipment damaged or not secured (specify) | B | Principal | 06/01/22 | Details |
04/06/22 | Storage room beside 24 | inappropriate storage of materials/furniture/shelving, or clutter | B | Principal | 06/01/22 | Details |
04/06/22 | 25 | equipment damaged or not secured (specify) | B | Principal | 06/01/22 | Details |
04/06/22 | 27 | fire exit route sign (yellow TDSB) - not posted / requires updating | B | Principal | 06/01/22 | Details |
05/02/22 | 114 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Principal | 06/01/22 | Details |
05/02/22 | 115 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Principal | 06/01/22 | Details |
05/02/22 | meter room | eyewash station required or in need of repair (specify) | A | Principal | 06/01/22 | Details |
05/02/22 | mech room by E6 | lighting is insufficient for task in work area, room number and why | B | Principal | 06/01/22 | Details |
05/02/22 | mech room by E6 | eyewash station required or in need of repair (specify) | A | Principal | 06/01/22 | Details |
05/02/22 | electrical room | trip hazard (i.e. flooring, other materials) | A | Principal | 06/01/22 | Details |
05/02/22 | Fan Room 1 | lighting is insufficient for task in work area, room number and why | B | Principal | 06/01/22 | Details |
05/02/22 | 117B (in Music Rm) | ceiling damaged (specify) | A | Principal | 06/01/22 | Details |
05/02/22 | 117A (in Music Rm) | insufficient means of communication (ie: PA, radio, etc.) | B | Principal | 06/01/22 | Details |
05/02/22 | 117A (in Music Rm) | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Principal | 06/01/22 | Details |
05/02/22 | Fan room above music room | extinguisher - tag missing or annual inspection more than 3 months overdue | A | Principal | 06/01/22 | Details |
05/02/22 | 101 | trip hazard (i.e. flooring, other materials) | A | Principal | 06/01/22 | Details |
05/02/22 | 101 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Principal | 06/01/22 | Details |
05/02/22 | 103 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Principal | 06/01/22 | Details |
05/02/22 | Prep Room | insufficient means of communication (ie: PA, radio, etc.) | B | Principal | 06/01/22 | Details |
05/02/22 | Prep Room | ceiling tiles missing/loose | A | Principal | 06/01/22 | Details |
05/02/22 | library | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Principal | 06/01/22 | Details |
05/02/22 | 228 prep | ceiling tiles missing/loose | A | Principal | 06/01/22 | Details |
05/02/22 | science storage | eyewash station required or in need of repair (specify) | A | Principal | 06/01/22 | Details |
06/29/22 | pool filter room | inappropriate storage of materials/furniture/shelving, or clutter | B | | | Details |
06/29/22 | Runnymede CI Health & Safety Bulletin Board | Health & Safety bulletin board - required items are missing or outdated (be specific) | B | | | Details |
06/29/22 | Mountainview Alt Health & Safety Bulletin | Health & Safety bulletin board - required items are missing or outdated (be specific) | B | | | Details |
06/29/22 | Main Boiler Room | leaking/pooling of liquid/water on equipment (be as specific as possible) | A | | | Details |
06/29/22 | old boiler room | leaking/pooling of liquid/water on equipment (be as specific as possible) | A | | | Details |
06/29/22 | Mountainview Alternative | egress blocked or insufficient path (doorway, hallway or stairwell) | B | | | Details |