Charles Gordon Senior Public School (GR. 07-08)

Health and Safety (H&S) workplace inspections are conducted every month in all of our 582 operating schools. Below you can find the H&S reports for your school, for the 2021-2022 school years.  More information and Frequently Asked Questions

Date InspectedLocation in SchoolHealth & Safety Issue ObservedClassAction Taken ByDate Action TakenDetails
09/09/21310paint flaking, chipping, possible lead exposureAPrincipal10/01/21Details
10/29/213rd floor hallwayceiling damaged (specify)ACaretaker11/09/21Details
10/29/21308ceiling damaged (specify)ACaretaker11/09/21Details
10/29/21311lighting in need of repair (maintenance issue)ACaretaker11/09/21Details
10/29/21310lighting in need of repair (maintenance issue)ACaretaker11/09/21Details
10/29/21305trip hazard (i.e. flooring, other materials)ACaretaker11/09/21Details
10/29/213rd floor exit 3ceiling tiles missing/looseACaretaker11/09/21Details
10/29/21Exit 3 (door to outside)lighting in need of repair (maintenance issue)ACaretaker11/09/21Details
10/29/21101leaking/pooling/ponding of liquid (specify liquid and source if possible)ACaretaker11/09/21Details
10/29/21310exposed wiring/damaged cord/ground pin missingACaretaker11/09/21Details
10/29/21306trip hazard (i.e. flooring, other materials)ACaretaker11/09/21Details
11/03/21Boiler Room (Roof)equipment damaged or not secured (specify)B  Details
11/03/21Boiler Room (Roof)ACM - insulation material damaged, possible ACMA1  Details
11/03/21Mech Room 1extinguisher - tag missing or annual inspection more than 3 months overdueACaretaker11/09/21Details
11/03/21Fan Room (roof)extinguisher - tag missing or annual inspection more than 3 months overdueACaretaker11/09/21Details
11/03/213rd floor hallwayexposed wiring/damaged cord/ground pin missingACaretaker03/01/22Details
11/03/213rd floor hallwayceiling damaged (specify)ACaretaker11/09/21Details
11/03/213rd floor hallwayceiling tiles missing/looseACaretaker11/09/21Details
11/03/21Mechanical Room - 3rd Floorextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker11/09/21Details
11/03/21Mechanical Room - 3rd Floorlighting in need of repair (maintenance issue)ACaretaker11/09/21Details
11/03/21304Hand hygiene - tap with soap and water OR hand sanitizer is not available (where required))BCaretaker03/01/22Details
11/03/21304inappropriate storage of materials/furniture/shelving, or clutterB  Details
11/03/21304lighting in need of repair (maintenance issue)ACaretaker11/09/21Details
11/03/21Fan Room (roof)extinguisher - tag missing or annual inspection more than 3 months overdueACaretaker11/09/21Details
11/03/21Boiler Room (Roof)door/access door (specify)A  Details
11/03/21Mech Room 1panel (specify)A  Details
11/03/21Roof step railingequipment damaged or not secured (specify)B  Details
11/03/21Mech Room 1paint flaking, chipping, possible lead exposureA  Details
11/03/21Exit 1 Hallwayceiling damaged (specify)ACaretaker11/09/21Details
11/03/21electrical room by main entrancelighting in need of repair (maintenance issue)ACaretaker03/01/22Details
11/03/21electrical room by main entrancebleach is present, where not permitted or not properly storedBCaretaker11/09/21Details
12/22/21Kitchenbleach is present, where not permitted or not properly storedBCaretaker02/01/22Details
02/03/22Boilerunable to inspect (specify why if possible)B  Details
02/03/22201air - return/supply (specify)A  Details
02/03/22208fire exit route sign (yellow TDSB) - not posted / requires updatingB  Details
02/03/22201insufficient means of communication (ie: PA, radio, etc.)B  Details
03/21/22104 Roboticspaint flaking, chipping, possible lead exposureAPrincipal05/02/22Details
03/21/22103door/access door (specify)APrincipal05/02/22Details
03/21/22103paint flaking, chipping, possible lead exposureAPrincipal05/02/22Details
03/21/22105trip hazard (i.e. flooring, other materials)APrincipal05/02/22Details
03/21/22310panel (specify)APrincipal05/02/22Details
03/21/22105display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls)BPrincipal05/02/22Details
04/26/22Caretaker’s Storage (by exit 3)unable to inspect (specify why if possible)BPrincipal04/27/22Details
04/26/22Staff Work Rm.furniture unsafe - requires repairAPrincipal04/27/22Details
04/27/223rd floor hallwayceiling tiles missing/looseAPrincipal05/02/22Details
04/27/22staffroomWorkplace Inspection Report posted?BPrincipal05/02/22Details
04/27/22staffroomJoint Health & Safety Committee meeting minutes - latest copy not postedBPrincipal05/02/22Details
05/17/22Machine Roomdoors not numbered properly (interior or exterior)B  Details
05/17/22electrical - hot water tank roomeyewash station required or in need of repair (specify)A  Details