Health and Safety (H&S) workplace inspections are conducted every month in all of our 582 operating schools. Below you can find the H&S reports for your school, for the 2019-2020 and 2020-2021 school years.  More information and Frequently Asked Questions

Date InspectedLocation in SchoolHealth & Safety Issue ObservedClassAction Taken ByDate Action TakenDetails
09/06/19Mechanical Room 224exposed wiring/damaged cord/ground pin missingACaretaker10/25/19Details
09/06/19Mechanical Room 224inappropriate storage of materials/furniture/shelving, or clutterBCaretaker09/24/19Details
09/06/19Hallwayceiling damaged (specify)ACaretaker10/25/19Details
09/06/19Office - Guidance 266 Rooms (A-J)ceiling damaged (specify)ACaretaker10/25/19Details
09/06/19Hallwayceiling damaged (specify)ACaretaker10/25/19Details
09/06/198ceiling damaged (specify)ACaretaker09/24/19Details
09/06/1911ceiling tiles missingACaretaker10/10/19Details
09/06/19Mechanical Room 268 Upperceiling damaged (specify)ACaretaker10/25/19Details
09/06/19147 Prep Roominspections not up to date (specify equipment)BPrincipal10/18/19Details
09/06/19Mechanical Room 002 - Boilerinappropriate storage of materials/furniture/shelving, or clutterBCaretaker09/24/19Details
10/28/19362door/access door (specify)ACaretaker11/21/19Details
10/28/19371extension cord/power bar - inappropriate use of extension cord/power bar (be specific)BPrincipal12/02/19Details
10/28/19367Awindow damaged, in need of repair (specify)APrincipal11/29/19Details
10/28/19362Bceiling damaged (specify)ACaretaker11/21/19Details
10/28/19Stairsfire separating doors in hallways/corridors being propped open (not classroom doors)BCaretaker11/06/19Details
10/28/19371ceiling damaged (specify)ACaretaker12/02/19Details
10/28/195exposed wiring/damaged cord/ground pin missingACaretaker11/02/19Details
10/28/19140 Prep Roominspections not up to date (specify equipment)BPrincipal11/29/19Details
10/28/19379ceiling damaged (specify)ACaretaker11/02/19Details
11/30/19147 Prep Roomfume hood - improper use (not to be used for storage)BPrincipal12/02/19Details
11/30/19145fume hood - improper use (not to be used for storage)BPrincipal12/02/19Details
11/30/19141 Prep Roomfume hood - improper use (not to be used for storage)BPrincipal12/02/19Details
11/30/19137 Prep Roomfume hood - improper use (not to be used for storage)BPrincipal12/02/19Details
11/30/19142extinguisher - tag missing or annual inspection more than 3 months overdueACaretaker12/02/19Details
11/30/19115guarding or shielding not in placeACaretaker12/12/19Details
11/30/19118Clighting in need of repair (maintenance issue)ACaretaker12/24/19Details
11/30/1913lighting in need of repair (maintenance issue)ACaretaker12/13/19Details
11/30/1913lighting in need of repair (maintenance issue)ACaretaker12/13/19Details
11/30/199window damaged, in need of repair (specify)ACaretaker12/02/19Details
11/30/19129ceiling damaged (specify)ACaretaker12/11/19Details
11/30/19119ceiling damaged (specify)ACaretaker12/11/19Details
11/30/19115ceiling damaged (specify)ACaretaker12/12/19Details
11/30/19153ceiling damaged (specify)ACaretaker12/13/19Details
11/30/19147 Prep Roomceiling damaged (specify)ACaretaker12/13/19Details
11/30/19118 Libraryceiling tiles missingACaretaker12/13/19Details
11/30/1911ceiling tiles missingACaretaker12/12/19Details
11/30/19125fume hood - improper use (not to be used for storage)BPrincipal12/02/19Details
12/05/195emergency exit door - mechanical malfunction on exit doorACaretaker12/06/19Details
12/05/19156window covering recommended on 1st floor (emergency lockdown procedures)BCaretaker12/06/19Details
01/15/20255Cimproper storage of flammable/combustible material BPrincipal01/16/20Details
01/15/20255 Dramaexposed wiring/damaged cord/ground pin missingACaretaker01/21/20Details
01/15/20239leaking/pooling/ponding of liquid (specify liquid and source if possible)ACaretaker01/16/20Details
01/15/20Mechanical Room 355receptacle/light switch (specify)ACaretaker01/16/20Details
02/05/20147 Prep Roomceiling damaged (specify)ACaretaker02/24/20Details
02/05/20167extension cord/power bar - inappropriate use of extension cord/power bar (be specific)BPrincipal05/01/20Details
02/05/20Hallwayceiling damaged (specify)ACaretaker03/03/20Details
02/05/20Office - Main 273ceiling damaged (specify)ACaretaker03/05/20Details
02/05/20Office - Main 273ceiling damaged (specify)ACaretaker03/05/20Details
02/05/20Office - Main 273ceiling damaged (specify)ACaretaker03/05/20Details
02/05/20Office - COOP 264ceiling damaged (specify)ACaretaker02/24/20Details
02/05/20Office - Guidance 266 Rooms (A-J)ceiling damaged (specify)ACaretaker03/03/20Details
02/05/20Office - Guidance 266 Rooms (A-J)ceiling damaged (specify)ACaretaker03/03/20Details
02/05/20Hallwayceiling damaged (specify)ACaretaker02/24/20Details
02/05/20268equipment damaged or not securedBCaretaker02/10/20Details
02/05/20Office A/V 260/262equipment damaged or not securedBCaretaker02/24/20Details
02/05/20Hallwayceiling damaged (specify)ACaretaker02/24/20Details
02/05/20265ceiling damaged (specify)ACaretaker02/24/20Details
02/05/20254fire exit route sign (yellow TDSB) - not posted / requires updatingBPrincipal02/20/20Details
02/05/20268ceiling damaged (specify)ACaretaker02/24/20Details
02/05/20254ceiling damaged (specify)ACaretaker03/03/20Details
03/03/20015 Cafeteriaemergency exits requires review by OH&S. Specify immediate concernA1Caretaker03/12/20Details
03/03/20Hallwayceiling damaged (specify)ACaretaker03/06/20Details
03/03/20Mechanical Room 268 Upperceiling damaged (specify)ACaretaker03/31/20Details
03/03/20Hallwayceiling damaged (specify)ACaretaker03/13/20Details
03/03/20Hallwayceiling damaged (specify)ACaretaker03/13/20Details
03/03/20015 Cafeteriaceiling damaged (specify)ACaretaker03/12/20Details
03/03/20Office - Tech 004ceiling damaged (specify)ACaretaker03/12/20Details
03/03/205equipment damaged or not securedBCaretaker03/12/20Details
05/21/20140 Prep Roomfume hood - there is no power to the fume hood in the chemical prep roomAPrincipal07/01/20Details
06/30/20Courtyardvegetation (please specify concern)ACaretaker07/07/20Details
06/30/20185receptacle/light switch (specify)ACaretaker07/07/20Details
06/30/20185damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACaretaker07/07/20Details
06/30/20Boilerleaking/pooling/ponding of liquid (specify liquid and source if possible)ACaretaker07/02/20Details
06/30/20104ceiling damaged (specify)ACaretaker07/21/20Details
06/30/20Stair 10ceiling damaged (specify)ACaretaker07/07/20Details
06/30/20154ceiling tiles missingACaretaker07/21/20Details
06/30/20156ceiling tiles missingACaretaker07/21/20Details
06/30/20185ceiling tiles missingACaretaker07/16/20Details
06/30/20187ceiling tiles missingACaretaker07/16/20Details
06/30/20107ceiling tiles missingACaretaker07/16/20Details
06/30/20111ceiling tiles missingACaretaker07/21/20Details
06/30/20109unable to inspect (specify why if possible)BCaretaker07/07/20Details
06/30/20Courtyardvegetation (please specify concern)ACaretaker07/07/20Details
07/14/209anti-slip strips missingBPrincipal08/26/20Details
07/14/205anti-slip strips missingBPrincipal08/26/20Details
07/14/205anti-slip strips missingBPrincipal08/26/20Details
07/14/209anti-slip strips missingBPrincipal08/26/20Details
07/14/209anti-slip strips missingBPrincipal08/26/20Details
07/14/209anti-slip strips missingBPrincipal08/26/20Details
07/14/209anti-slip strips missingBPrincipal08/26/20Details
07/14/2013anti-slip strips missingBPrincipal08/26/20Details
07/14/2013anti-slip strips missingBPrincipal08/26/20Details
07/14/2013anti-slip strips missingBPrincipal08/26/20Details
07/14/20137 Prep Roomfume hood - there is no power to the fume hood in the chemical prep roomACaretaker07/16/20Details
07/14/20141 Prep Roomfume hood - there is no power to the fume hood in the chemical prep roomACaretaker07/16/20Details
07/14/20Roof Accessevidence of pests (interior or exterior), be as specific as possible.ACaretaker07/22/20Details
07/14/20Roof Accessroof access/walkway hazardous (specify)ACaretaker07/16/20Details
07/14/20Groundsroof access/walkway hazardous (specify)ACaretaker07/22/20Details
07/14/2011ceiling damaged (specify)ACaretaker08/11/20Details
07/14/2011ceiling damaged (specify)ACaretaker08/11/20Details
07/14/20Old Boiler Rmleaking/pooling/ponding of liquid (specify liquid and source if possible)ACaretaker07/16/20Details
07/14/20Roofleaking/pooling/ponding of liquid (specify liquid and source if possible)ACaretaker07/21/20Details
07/14/20Roofleaking/pooling/ponding of liquid (specify liquid and source if possible)ACaretaker07/21/20Details
07/14/20Roofleaking/pooling/ponding of liquid (specify liquid and source if possible)ACaretaker07/21/20Details
07/14/20Roofleaking/pooling/ponding of liquid (specify liquid and source if possible)ACaretaker07/21/20Details
07/14/20Roofvegetation (please specify concern)ACaretaker07/21/20Details
08/24/20Groundsuneven surface - driveway, parking lot, walkway, or otherACaretaker08/25/20Details
09/03/20135display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls)BPrincipal09/18/20Details
09/03/20142ceiling damaged (specify)ACaretaker09/18/20Details
09/03/20Office - Tech 004ceiling damaged (specify)ACaretaker09/18/20Details
10/14/20266iceiling damaged (specify)ACaretaker10/23/20Details
10/14/20015 Cafeteriaemergency exits requires review by OH&S. Specify immediate concernA1Caretaker10/21/20Details
10/14/20141 Prep Roomdoor/access door (specify)ACaretaker10/22/20Details
10/14/205equipment damaged or not securedBPrincipal10/19/20Details
10/14/20Building Wideextension cord/power bar - inappropriate use of extension cord/power bar (be specific)BPrincipal10/15/20Details
11/04/209eyewash station required or in need of repair (specify)ACaretaker11/06/20Details
11/04/20135eyewash station required or in need of repair (specify)ACaretaker11/06/20Details
11/04/20Mechanical Room 355eyewash station required or in need of repair (specify)ACaretaker11/06/20Details
11/04/20school widefire separating doors in hallways/corridors being propped open (not classroom doors)BCaretaker11/16/20Details
11/04/209display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls)BPrincipal12/04/20Details
11/04/209anti-slip strips missingBPrincipal11/06/20Details
11/04/20271doors not numbered properly (interior or exterior)BPrincipal12/04/20Details
12/31/20156window covering recommended on 1st floor (emergency lockdown procedures)BPrincipal02/04/21Details
01/27/21Mechanical Room 220ceiling tiles missingACaretaker01/28/21Details
01/27/21242inappropriate storage of materials/furniture/shelving, or clutterBPrincipal02/04/21Details
01/27/21242ceiling tiles missingACaretaker01/28/21Details
01/27/21Stair 9ceiling damaged (specify)ACaretaker01/28/21Details
01/27/21Mechanical Room 224ceiling damaged (specify)ACaretaker01/28/21Details
01/27/21Hallwayceiling damaged (specify)ACaretaker02/02/21Details
01/27/21Hallwayceiling damaged (specify)ACaretaker01/28/21Details
01/27/21Exit 3ceiling damaged (specify)ACaretaker02/09/21Details
01/27/21259 Auditoriumceiling damaged (specify)ACaretaker01/28/21Details
01/27/21241ceiling damaged (specify)ACaretaker02/09/21Details
01/27/21Stair 7ceiling damaged (specify)ACaretaker01/28/21Details
01/27/21Hallwayceiling damaged (specify)ACaretaker02/09/21Details
01/27/21250window damaged, in need of repair (specify)ACaretaker01/28/21Details
01/27/21252window damaged, in need of repair (specify)ACaretaker01/28/21Details
01/27/21250paint flaking, chipping, possible lead exposureACaretaker01/28/21Details
01/27/21259 Auditoriumdamaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACaretaker01/28/21Details
01/27/21222 Balconylighting in need of repair (maintenance issue)ACaretaker01/28/21Details
01/27/21251lighting in need of repair (maintenance issue)ACaretaker02/09/21Details
01/27/21240 Girl's Wahroomdoor/access door (specify)ACaretaker01/28/21Details
01/27/21255 Dramaceiling tiles missingACaretaker02/09/21Details
01/29/219equipment damaged or not securedBPrincipal02/05/21Details
01/29/21Mechanical Room 355eyewash station required or in need of repair (specify)ACaretaker02/08/21Details
01/29/219eyewash station required or in need of repair (specify)APrincipal02/05/21Details
01/29/2113guarding or shielding not in placeACaretaker02/08/21Details
01/29/21Boilerextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker02/08/21Details
01/29/2113anti-slip strips missingBPrincipal02/04/21Details
01/29/219anti-slip strips missingBPrincipal02/04/21Details
01/29/215anti-slip strips missingBPrincipal02/04/21Details
01/29/21137 Prep Roomspill procedures are not postedBPrincipal03/03/21Details
01/29/21137 Prep Roomspill kit or bucket of sand is not availableBPrincipal03/03/21Details
01/29/21137 Prep Roomspill kit or bucket of sand is not availableBPrincipal02/05/21Details
01/29/21137 Prep Roomwaste containers are not available or properly labelled as required in Science Prep RoomBPrincipal03/03/21Details
01/29/21140 Prep Roombroken glass container is required in science storage/prep roomBPrincipal03/03/21Details
01/29/21137 Prep RoomTDSB Chemical Storage poster not visible Science Prep RoomBPrincipal03/03/21Details
01/29/21276 Staff RoomJoint Health & Safety Committee 'Terms of Reference' posted?BPrincipal02/05/21Details
01/29/21258 slop sinkceiling tiles missingACaretaker02/09/21Details
01/29/21262ceiling tiles missingACaretaker02/09/21Details
01/29/21269extension cord/power bar - inappropriate use of extension cord/power bar (be specific)BPrincipal04/20/21Details
01/29/215extension cord/power bar - inappropriate use of extension cord/power bar (be specific)BPrincipal04/20/21Details
01/29/21137 Prep RoomPPE - personal protective equipment not availableBPrincipal03/03/21Details
01/29/21266microwave stickers missingBPrincipal03/05/21Details
01/29/21254equipment damaged or not securedBCaretaker02/17/21Details
01/29/215equipment damaged or not securedBPrincipal02/05/21Details
03/01/21140 Prep Roombroken glass container is required in science storage/prep roomBPrincipal03/03/21Details
03/01/21137 Prep RoomTDSB Chemical Storage poster not visible Science Prep RoomBPrincipal03/03/21Details
03/01/21137 Prep Roomwaste containers are not available or properly labelled as required in Science Prep RoomBPrincipal03/03/21Details
03/01/21137 Prep Roomspill kit or bucket of sand is not availableBPrincipal03/03/21Details
03/01/21137 Prep Roomspill procedures are not postedBPrincipal03/03/21Details
03/01/2113anti-slip strips missingBPrincipal03/03/21Details
03/01/215anti-slip strips missingBPrincipal03/03/21Details
03/01/219anti-slip strips missingBPrincipal03/03/21Details
03/01/21Mechanical Room 355extinguisher - tag missing or annual inspection more than 3 months overdueACaretaker03/09/21Details
03/01/2113guarding or shielding not in placeACaretaker03/03/21Details
03/01/21Mechanical Room 355eyewash station required or in need of repair (specify)ACaretaker03/03/21Details
03/01/215equipment damaged or not securedBPrincipal04/20/21Details
03/01/219equipment damaged or not securedBPrincipal03/03/21Details
03/01/21137 Prep RoomPPE - personal protective equipment not availableBPrincipal03/03/21Details
03/01/21015Hpanel (specify) ACaretaker03/03/21Details
03/01/21015Gpanel (specify) ACaretaker03/03/21Details
03/01/215extension cord/power bar - inappropriate use of extension cord/power bar (be specific)BPrincipal04/20/21Details
03/01/21002 - Tech Education Officeceiling tiles missingACaretaker03/12/21Details
03/01/21Hallwayceiling tiles missingACaretaker03/12/21Details
03/01/21140 Prep Roomcarts for transporting chemicals do not have 4 sidesBPrincipal03/03/21Details
03/31/21Mechanical Room 355trip hazard (i.e. flooring, other materials)ACaretaker05/21/21Details
03/31/21140 Prep Roomdoor/access door (specify)ACaretaker06/14/21Details
03/31/21352fire exit route sign (yellow TDSB) - not posted / requires updatingBPrincipal05/03/21Details
03/31/21Mechanical Room 001 - Chillerinspections not up to date (specify equipment)BCaretaker05/03/21Details
06/29/21156lighting in need of repair (maintenance issue)A  Details
06/29/21164receptacle/light switch (specify)ACaretaker07/06/21Details
06/29/21160Adoor/access door (specify)A  Details
06/29/21Boilerexposed wiring/damaged cord/ground pin missingA  Details
06/29/21102exposed wiring/damaged cord/ground pin missingACaretaker06/30/21Details
06/29/21104exposed wiring/damaged cord/ground pin missingA  Details
06/29/21Boilerinappropriate storage of materials/furniture/shelving, or clutterB  Details
06/29/21154lighting in need of repair (maintenance issue)A  Details
06/29/21183lighting in need of repair (maintenance issue)A  Details
06/29/21164lighting in need of repair (maintenance issue)A  Details
06/29/21Girl's Washroomlighting in need of repair (maintenance issue)A  Details
06/29/21All Gender Washroomlighting in need of repair (maintenance issue)A  Details
06/29/21Staff Washroomlighting in need of repair (maintenance issue)A  Details
06/29/21Boy's Washroomlighting in need of repair (maintenance issue)A  Details
06/29/21Mechanical Room 173paint flaking, chipping, possible lead exposureACaretaker06/30/21Details
06/29/21175paint flaking, chipping, possible lead exposureACaretaker07/06/21Details
06/29/21167paint flaking, chipping, possible lead exposureACaretaker07/06/21Details
06/29/21177paint flaking, chipping, possible lead exposureACaretaker07/06/21Details
06/29/21Girl's Change roompaint flaking, chipping, possible lead exposureACaretaker07/06/21Details
06/29/21Hallwayceiling damaged (specify)A  Details
06/29/21107ceiling damaged (specify)A  Details
06/29/21101ceiling damaged (specify)A  Details
06/29/21156ceiling tiles missingA  Details
06/29/21154ceiling tiles missingA  Details
06/29/21183ceiling tiles missingACaretaker06/30/21Details
06/29/21185ceiling tiles missingACaretaker06/30/21Details
06/29/21164ceiling tiles missingA  Details
06/29/21Stair 11ceiling tiles missingA  Details
06/29/21169ceiling tiles missingA  Details
06/29/21106ceiling tiles missingA  Details
06/29/21113ceiling tiles missingA  Details
06/29/21111ceiling tiles missingA  Details