Date Inspected | Location in School | Health & Safety Issue Observed | Class | Action Taken By | Date Action Taken | Details |
09/27/21 | Boiler Room. | panel (specify) | A | Caretaker | 11/17/21 | Details |
09/27/21 | Boiler Room. | eyewash station required or in need of repair (specify) | A | Caretaker | 11/17/21 | Details |
09/27/21 | Hallway near room 244 | leaking/pooling/ponding of water or liquid (be as specific as possible) | A | Caretaker | 11/04/21 | Details |
10/21/21 | 350 Chemical Storage | eyewash station required or in need of repair (specify) | A | Principal | 11/15/21 | Details |
10/21/21 | 391 | lighting in need of repair (maintenance issue) | A | Caretaker | 12/01/21 | Details |
10/21/21 | 385 | lighting in need of repair (maintenance issue) | A | Caretaker | 12/01/21 | Details |
10/21/21 | 379 | ceiling tiles missing/loose | A | Caretaker | 12/01/21 | Details |
10/21/21 | hall | guarding or shielding not in place | A | Caretaker | 12/01/21 | Details |
10/21/21 | hall | guarding or shielding not in place | A | Caretaker | 12/01/21 | Details |
10/21/21 | 377 | ceiling tiles missing/loose | A | Caretaker | 12/01/21 | Details |
10/21/21 | 377 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Principal | 11/15/21 | Details |
10/21/21 | 370 Fan Rm 3rd fl | lighting in need of repair (maintenance issue) | A | Caretaker | 12/01/21 | Details |
10/21/21 | 350 Chemical Storage | waste containers are not available or properly labelled as required in Science Prep Room | B | Principal | 11/15/21 | Details |
10/21/21 | 350 Chemical Storage | TDSB Chemical Storage poster not visible Science Prep Room | B | Principal | 11/15/21 | Details |
10/21/21 | 350 Chemical Storage | spill procedures are not posted | B | Principal | 11/15/21 | Details |
10/21/21 | 346 | extinguisher - tag missing or annual inspection more than 3 months overdue | A | Caretaker | 12/01/21 | Details |
10/21/21 | 19A - Fan Room | guarding or shielding not in place | A | Caretaker | 12/01/21 | Details |
10/21/21 | 100 | paint flaking, chipping, possible lead exposure | A | Caretaker | 12/01/21 | Details |
10/21/21 | boiler room | ACM - insulation material damaged, possible ACM | A1 | Caretaker | 12/01/21 | Details |
10/21/21 | 170 Machine repair Shop | eyewash station required or in need of repair (specify) | A | Caretaker | 12/01/21 | Details |
10/21/21 | 174 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Principal | 11/15/21 | Details |
10/21/21 | 169 welding shop | panel (specify) | A | Caretaker | 12/01/21 | Details |
11/02/21 | 109 | paint flaking, chipping, possible lead exposure | A | Caretaker | 12/01/21 | Details |
11/02/21 | 338 Prep Room | ceiling damaged (specify) | A | Caretaker | 01/04/22 | Details |
11/02/21 | 364 | trip hazard (i.e. flooring, other materials) | A | Caretaker | 01/04/22 | Details |
11/02/21 | 363 | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 01/04/22 | Details |
11/02/21 | 366 | trip hazard (i.e. flooring, other materials) | A | Caretaker | 01/04/22 | Details |
11/02/21 | 352 | fire exit route sign (yellow TDSB) - not posted / requires updating | B | Principal | 11/29/21 | Details |
11/02/21 | 349 | inappropriate storage of materials/furniture/shelving, or clutter | B | Principal | 01/06/22 | Details |
11/02/21 | 345 prep | fire exit route sign (yellow TDSB) - not posted / requires updating | B | Principal | 11/29/21 | Details |
11/02/21 | 354 | fire exit route sign (yellow TDSB) - not posted / requires updating | B | Principal | 11/29/21 | Details |
12/17/21 | 26 Pump Room | paint flaking, chipping, possible lead exposure | A | Caretaker | 01/04/22 | Details |
12/17/21 | 109 Auto | paint flaking, chipping, possible lead exposure | A | Caretaker | 01/04/22 | Details |
12/17/21 | 2nd Floor Western Hallway | paint flaking, chipping, possible lead exposure | A | Caretaker | 01/04/22 | Details |
01/17/22 | 176A | inappropriate storage of materials/furniture/shelving, or clutter | B | Caretaker | 05/04/22 | Details |
01/17/22 | 174 | ceiling tiles missing/loose | A | Caretaker | 05/04/22 | Details |
01/17/22 | 169 welding shop | ventilation (specify) | A | Caretaker | 05/04/22 | Details |
01/17/22 | fan room 500 | insulation - required or in need of repair | A | Caretaker | 05/04/22 | Details |
01/17/22 | 174b | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | | | Details |
01/20/22 | 174A | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | | | Details |
01/20/22 | 1st floor hallway by shops | ceiling damaged (specify) | A | Caretaker | 05/04/22 | Details |
01/20/22 | Student School 3rd Floor Hall | egress blocked or insufficient path (doorway, hallway or stairwell) | B | | | Details |
01/20/22 | Health & Safety Bulletin Board by 267 | Health & Safety bulletin board - required items are missing or outdated (be specific) | B | | | Details |
01/20/22 | Drum Practice Room in 102A | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 05/04/22 | Details |
01/20/22 | 102 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | | | Details |
01/20/22 | 109 auto shop | insulation - required or in need of repair | A | Caretaker | 05/04/22 | Details |
01/20/22 | chemistry prep room | eyewash station required or in need of repair (specify) | A | Caretaker | 05/04/22 | Details |
01/20/22 | tech office | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | | | Details |
02/10/22 | 173 Shop | ceiling tiles missing/loose | A | | | Details |
02/10/22 | 155 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Principal | 04/06/22 | Details |
02/10/22 | 171 machine shop | ceiling tiles missing/loose | A | | | Details |
02/10/22 | 166 | panel (specify) | A | | | Details |
02/10/22 | 169 welding shop | equipment damaged or not secured (specify) | A | | | Details |
02/10/22 | 167 Wood Shop. | trip hazard (i.e. flooring, other materials) | A | Caretaker | 05/04/22 | Details |
02/10/22 | 167 Wood Shop. | anti-slip strips missing | B | Principal | 04/06/22 | Details |
02/10/22 | 100 auto shop | guarding or shielding not in place | A | Caretaker | 05/04/22 | Details |
02/10/22 | 100 auto shop | guarding or shielding not in place | A | Caretaker | 05/04/22 | Details |
02/10/22 | 100 auto shop | gas cylinder not secured | A | Principal | 04/06/22 | Details |
02/10/22 | 100 auto shop | gas cylinder not secured | B | Principal | 04/06/22 | Details |
02/10/22 | 100 auto shop | anti-slip strips missing | A | Principal | 04/06/22 | Details |
02/10/22 | 100 auto shop | trip hazard (i.e. flooring, other materials) | A | Caretaker | 05/04/22 | Details |
02/10/22 | 109 Auto | anti-slip strips missing | A | Principal | 04/06/22 | Details |
02/10/22 | 155 | receptacle/light switch (specify) | A | Caretaker | 05/05/22 | Details |
02/10/22 | 109 Auto | trip hazard (i.e. flooring, other materials) | A | Caretaker | 05/04/22 | Details |
03/09/22 | Hallway by elevator 368 | ceiling tiles missing/loose | A | | | Details |
03/09/22 | 346 chem prep | NO FOOD & DRINK Sticker - not present or not being observed | B | | | Details |
03/09/22 | 346 chem prep | spill procedures are not posted | B | | | Details |
03/09/22 | 346 chem prep | eyewash station required or in need of repair (specify) | A | | | Details |
03/09/22 | 350 Chemical Storage | eyewash station required or in need of repair (specify) | A | | | Details |
03/09/22 | Staff room (Western) | Joint Health & Safety Committee meeting minutes - latest copy not posted | B | | | Details |
03/09/22 | 263 (beside fan room) | ceiling tiles missing/loose | A | | | Details |
04/21/22 | staff room | Workplace Inspection Report posted? | B | | | Details |
04/21/22 | 210 | ceiling damaged (specify) | A | | | Details |
04/21/22 | 209 | ceiling damaged (specify) | A | | | Details |
04/21/22 | 208 | lighting in need of repair (maintenance issue) | A | | | Details |
04/21/22 | 205 | ceiling damaged (specify) | A | | | Details |
04/21/22 | 205 | trip hazard (i.e. flooring, other materials) | A | | | Details |
04/21/22 | 109 Auto | ceiling damaged (specify) | A | | | Details |
04/21/22 | 26 Pump Room | mould | A | | | Details |
04/21/22 | 167 Wood Shop. | Procedures and Safe Use - signage not present for equipment in Tech Shop | B | | | Details |
04/21/22 | 167 Wood Shop. | fire exit route sign (yellow TDSB) - not posted / requires updating | B | | | Details |
04/21/22 | 173 Shop | leaking/pooling/ponding of water or liquid (be as specific as possible) | A | | | Details |
04/21/22 | 173 Shop | leaking/pooling/ponding of water or liquid (be as specific as possible) | A | | | Details |
04/21/22 | 109 Auto | ceiling damaged (specify) | A | | | Details |
04/21/22 | 203 | ceiling damaged (specify) | A | | | Details |
05/30/22 | 267 | bleach is present, where not permitted or not properly stored | B | | | Details |
05/30/22 | 267 | Health & Safety bulletin board - required items are missing or outdated (be specific) | B | | | Details |
05/30/22 | 109 auto shop | inspections not up to date (specify equipment) | B | | | Details |
05/30/22 | 109 auto shop | anti-slip strips missing | B | | | Details |
05/30/22 | 165 wood shop | anti-slip strips missing | B | | | Details |
05/30/22 | 165 wood shop | exposed wiring/damaged cord/ground pin missing | A | | | Details |
05/30/22 | 167 wood shop | eyewash station required or in need of repair (specify) | A | | | Details |
05/30/22 | 167 wood shop | anti-slip strips missing | B | | | Details |
05/30/22 | 100 auto shop | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | | | Details |
05/30/22 | 100 auto shop | anti-slip strips missing | B | | | Details |
05/30/22 | 100 auto shop | inspections not up to date (specify equipment) | B | | | Details |
05/30/22 | 169 welding shop | anti-slip strips missing | B | | | Details |
05/30/22 | 169 welding shop | carbon dioxide monitor inspection out of date (specify location) | A | | | Details |
05/30/22 | 169 welding shop | eyewash station required or in need of repair (specify) | A | | | Details |
05/30/22 | 173 Shop | equipment damaged or not secured (specify) | B | | | Details |
05/30/22 | 176 | anti-slip strips missing | B | | | Details |
05/30/22 | 176 | eyewash station required or in need of repair (specify) | A | | | Details |
05/30/22 | 176 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | | | Details |
05/30/22 | Boiler Room. | eyewash station required or in need of repair (specify) | A | | | Details |
05/30/22 | boiler room | guarding or shielding not in place | A | | | Details |
05/30/22 | Fan room 10 | guarding or shielding not in place | A | | | Details |
05/30/22 | 350 Chemical Storage | fire exit route sign (yellow TDSB) - not posted / requires updating | B | | | Details |
05/30/22 | fan room 443 | guarding or shielding not in place | A | | | Details |
05/30/22 | fan room 443 | guarding or shielding not in place | A | | | Details |
05/30/22 | fan room 370 | lighting is insufficient for task in work area, room number and why | B | | | Details |
05/30/22 | fan room 370 | guarding or shielding not in place | A | | | Details |
05/30/22 | 273 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | | | Details |
05/30/22 | 273 | fire exit route sign (yellow TDSB) - not posted / requires updating | B | | | Details |
05/30/22 | 270 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | | | Details |
05/30/22 | 272 | fire exit route sign (yellow TDSB) - not posted / requires updating | B | | | Details |
05/30/22 | 272 | panel (specify) | A | | | Details |
05/30/22 | Fan Rm above Staff Room | guarding or shielding not in place | A | | | Details |
06/24/22 | Team Room next to room 10 | exposed wiring/damaged cord/ground pin missing | A | | | Details |
06/24/22 | 254 | temperature does not meet TDSB Guideline | A | | | Details |
06/24/22 | 109 auto shop | paint flaking, chipping, possible lead exposure | A | | | Details |
06/24/22 | 100 auto shop | gas cylinder not secured | B | | | Details |
06/24/22 | chiller room | temperature does not meet TDSB Guideline | A | | | Details |
06/24/22 | 167 wood shop | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | | | Details |
06/24/22 | 169 welding shop | ventilation (specify) | A | | | Details |
06/24/22 | pool filter room | ventilation (specify) | A | | | Details |
06/24/22 | 235 storage | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | | | Details |
06/24/22 | 239 | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | | | Details |
06/24/22 | 242, 244, 250 & 251 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | | | Details |
06/24/22 | Doorway from 246 to 248 | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | | | Details |
06/24/22 | 237, 252, 253, 254 & hall | paint flaking, chipping, possible lead exposure | A | | | Details |
06/24/22 | Fan rooms 10, 370 & 443 | guarding or shielding not in place | A | | | Details |
06/24/22 | Electrical Rm 2 | inappropriate storage of materials/furniture/shelving, or clutter | B | | | Details |
06/24/22 | Science Prep Rm Inside 348 | eyewash station required or in need of repair (specify) | A | | | Details |
06/24/22 | Science Prep Rm Inside 348 | inspections not up to date (specify equipment) | B | | | Details |
06/24/22 | Health & Safety Bulletin Board by 267 | Health & Safety bulletin board - required items are missing or outdated (be specific) | B | | | Details |
06/24/22 | The Student School | egress blocked or insufficient path (doorway, hallway or stairwell) | B | | | Details |
06/24/22 | 3rd Floor Hall by E10 | egress blocked or insufficient path (doorway, hallway or stairwell) | B | | | Details |
06/24/22 | 236 | fire exit route sign (yellow TDSB) - not posted / requires updating | B | | | Details |