Date Inspected | Location in School | Health & Safety Issue Observed | Class | Action Taken By | Date Action Taken | Details |
09/18/23 | 404 | microwave stickers missing | B | Caretaker | 12/01/23 | Details |
09/18/23 | 416 | trip hazard (i.e. flooring, other materials) | A | Caretaker | 11/09/23 | Details |
09/18/23 | 348A Fan Room | unable to inspect (specify why if possible) | B | Caretaker | 11/01/23 | Details |
09/18/23 | 349 fan room | unable to inspect (specify why if possible) | B | Caretaker | 11/01/23 | Details |
09/18/23 | 343 Fan Room | unable to inspect (specify why if possible) | B | Caretaker | 11/01/23 | Details |
09/18/23 | 417 | ceiling damaged (specify) | A | Caretaker | 11/02/23 | Details |
09/18/23 | 257 Fan Room | unable to inspect (specify why if possible) | B | Caretaker | 11/01/23 | Details |
10/23/23 | Main Foyer | paint flaking, chipping, possible lead exposure | A | Caretaker | 12/01/23 | Details |
10/23/23 | Office Vault | inappropriate storage of materials/furniture/shelving, or clutter | B | Caretaker | 12/21/23 | Details |
10/23/23 | Main office kitchen | ceiling tiles missing/loose | A | Caretaker | 12/01/23 | Details |
10/23/23 | Main office hall | ceiling tiles missing/loose | A | Caretaker | 12/01/23 | Details |
11/08/23 | 343 Fan Room | unable to inspect (specify why if possible) | B | Caretaker | 12/21/23 | Details |
11/08/23 | 323 Prep Rm | ceiling tiles missing/loose | A | Caretaker | 01/17/24 | Details |
11/08/23 | 515 Fan Room | unable to inspect (specify why if possible) | B | Caretaker | 01/17/24 | Details |
11/08/23 | 348A Fan Room | unable to inspect (specify why if possible) | B | Caretaker | 01/16/24 | Details |
11/08/23 | 357 fan | unable to inspect (specify why if possible) | B | Caretaker | 12/21/23 | Details |
11/08/23 | 343 Fan Room | unable to inspect (specify why if possible) | B | Caretaker | 12/21/23 | Details |
11/08/23 | 225 | ceiling damaged (specify) | A | Caretaker | 01/22/24 | Details |
11/08/23 | 225 | equipment damaged or improperly stored (specify) | B | Caretaker | 01/18/24 | Details |
11/08/23 | 225 | equipment damaged or improperly stored (specify) | B | Caretaker | 01/18/24 | Details |
11/08/23 | 12AB | unable to inspect (specify why if possible) | B | Caretaker | 12/21/23 | Details |
11/08/23 | stage | unable to inspect (specify why if possible) | B | Caretaker | 01/22/24 | Details |
11/08/23 | Filter Room | unable to inspect (specify why if possible) | B | Caretaker | 12/21/23 | Details |
11/08/23 | Swim Pool | unable to inspect (specify why if possible) | B | Caretaker | 12/21/23 | Details |
11/08/23 | 257 Fan Room | unable to inspect (specify why if possible) | B | Caretaker | 12/21/23 | Details |
12/17/23 | 417 | paint flaking, chipping, possible lead exposure | A | Caretaker | 01/26/24 | Details |
12/17/23 | 416 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Caretaker | 03/07/24 | Details |
12/17/23 | Fan Room - 348A | unable to inspect (specify why if possible) | A | Caretaker | 02/26/24 | Details |
12/17/23 | Fan Room 257 | unable to inspect (specify why if possible) | A | Caretaker | 03/07/24 | Details |
12/17/23 | Filter Room Basement | unable to inspect (specify why if possible) | B | Caretaker | 01/29/24 | Details |
12/17/23 | 420 | microwave stickers missing | B | Caretaker | 01/26/24 | Details |
12/17/23 | 405 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Caretaker | 03/27/24 | Details |
12/17/23 | 357 Fan Room | unable to inspect (specify why if possible) | B | Caretaker | 03/07/24 | Details |
12/17/23 | Boiler Room 110 | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 01/29/24 | Details |
12/17/23 | 425 | ceiling tiles missing/loose | A | Caretaker | 02/27/24 | Details |
12/20/23 | Boiler Room 110 | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 01/29/24 | Details |
12/20/23 | 257 Fan Room | unable to inspect (specify why if possible) | B | Caretaker | 01/10/24 | Details |
12/20/23 | 343 Fan Room | unable to inspect (specify why if possible) | B | Caretaker | 01/10/24 | Details |
12/20/23 | 349 fan room | guarding or shielding not in place | A | Caretaker | 01/19/24 | Details |
12/20/23 | 357 Fan Room | unable to inspect (specify why if possible) | B | Caretaker | 01/19/24 | Details |
12/20/23 | Fan Room - 348A | unable to inspect (specify why if possible) | B | Caretaker | 01/10/24 | Details |
12/20/23 | 302 | temperature does not meet TDSB Guideline | A | Caretaker | 02/15/24 | Details |
12/20/23 | 323 | ceiling tiles missing/loose | A | Caretaker | 01/26/24 | Details |
12/20/23 | 320 | fume hood - improper use (not to be used for storage) | B | Caretaker | 02/26/24 | Details |
12/20/23 | Filter Room Basement | unable to inspect (specify why if possible) | B | Caretaker | 01/10/24 | Details |
12/20/23 | phone electrical room | leaking/pooling of liquid/water on equipment (be as specific as possible) | A | Caretaker | 01/29/24 | Details |
12/20/23 | 316 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Caretaker | 02/26/24 | Details |
12/20/23 | Boiler Room 110 | exposed wiring/damaged cord/ground pin missing | A | Caretaker | 01/29/24 | Details |
01/30/24 | 116 mechanical | eyewash station required or in need of repair (specify) | A | Caretaker | 03/20/24 | Details |
02/14/24 | 106 Boy w/rm | unable to inspect (specify why if possible) | B | Caretaker | 03/20/24 | Details |
02/14/24 | Boiler Room. | carbon dioxide monitor inspection out of date (specify location) | A | Caretaker | 03/27/24 | Details |
02/14/24 | library (first floor) | unable to inspect (specify why if possible) | B | Caretaker | 03/20/24 | Details |
02/14/24 | fan Room 116 | equipment damaged or improperly stored (specify) | B | Caretaker | 03/20/24 | Details |
02/25/24 | 241 | door/access door (specify) | A | Caretaker | 04/04/24 | Details |
02/25/24 | 235 | ceiling tiles missing/loose | A | Caretaker | 04/05/24 | Details |
02/25/24 | 230 | ceiling damaged (specify) | A | Caretaker | 04/05/24 | Details |
02/25/24 | 233 | ceiling damaged (specify) | A | Caretaker | 04/05/24 | Details |
02/25/24 | 231 | equipment damaged or improperly stored (specify) | B | Caretaker | 04/05/24 | Details |
03/15/24 | 126 a/v room | ACM - tiles broken/damaged, possible ACM | A | Caretaker | 04/16/24 | Details |
03/15/24 | 128 | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 05/02/24 | Details |
03/15/24 | 133 | ventilation (specify) | A | Caretaker | 04/04/24 | Details |
03/15/24 | 127 | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 05/02/24 | Details |
03/15/24 | 127 | ceiling tiles missing/loose | A | Caretaker | 05/01/24 | Details |
04/09/24 | 348A Fan Room | unable to inspect (specify why if possible) | B | Caretaker | 07/05/24 | Details |
04/09/24 | 349 fan room | equipment damaged or improperly stored (specify) | B | Caretaker | 07/08/24 | Details |
04/09/24 | 216 | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 06/24/24 | Details |
04/09/24 | 225 | eyewash station required or in need of repair (specify) | A | Caretaker | 07/05/24 | Details |
04/09/24 | stairwell | ceiling damaged (specify) | A | Caretaker | 07/08/24 | Details |
04/09/24 | 244 | ceiling damaged (specify) | A | Caretaker | 07/10/24 | Details |
04/09/24 | 246 | fire extinguisher not adequately charged or mounted | A | Caretaker | 07/08/24 | Details |
04/09/24 | 246 | inappropriate storage of materials/furniture/shelving, or clutter | B | Caretaker | 09/05/24 | Details |
04/09/24 | 227 | ceiling tiles missing/loose | A | Caretaker | 06/24/24 | Details |
04/09/24 | 231 | equipment damaged or improperly stored (specify) | B | Caretaker | 07/05/24 | Details |
04/09/24 | 231 | ceiling damaged (specify) | A | Caretaker | 07/05/24 | Details |
04/09/24 | 233 | lighting in need of repair (maintenance issue) | A | Caretaker | 07/10/24 | Details |
04/09/24 | 230 | ceiling damaged (specify) | A | Caretaker | 06/24/24 | Details |
04/09/24 | 230 | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 06/24/24 | Details |
04/09/24 | 235 | egress blocked or insufficient path (doorway, hallway or stairwell) | B | Caretaker | 07/10/24 | Details |
04/09/24 | 244 | ceiling damaged (specify) | A | Caretaker | 07/10/24 | Details |
05/24/24 | Hallway by 349 fanroom | equipment damaged or improperly stored (specify) | B | Caretaker | 07/22/24 | Details |
05/24/24 | Pool Gallery | egress blocked or insufficient path (doorway, hallway or stairwell) | B | Caretaker | 07/22/24 | Details |
05/24/24 | 249 | excessive dust (related to tech shops) | B | Caretaker | 08/12/24 | Details |
05/24/24 | Exit7 2nd floor | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 08/12/24 | Details |
05/24/24 | Fan Room 108 | ventilation (specify) | A | Caretaker | 08/12/24 | Details |
05/24/24 | 267 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Caretaker | 08/12/24 | Details |
05/24/24 | 264 | ceiling damaged (specify) | A | Caretaker | 07/22/24 | Details |
05/24/24 | 262 | lighting in need of repair (maintenance issue) | A | Caretaker | 08/12/24 | Details |
05/24/24 | 250 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Caretaker | 08/12/24 | Details |
05/24/24 | 266 Work Rm | lighting in need of repair (maintenance issue) | A | Caretaker | 08/13/24 | Details |