Date Inspected | Location in School | Health & Safety Issue Observed | Class | Action Taken By | Date Action Taken | Details |
09/06/23 | 306A | receptacle/light switch (specify) | A | Caretaker | 09/18/23 | Details |
09/06/23 | electrical room | combustibles stored in electrical room | A | Caretaker | 09/18/23 | Details |
09/06/23 | 215 A | safety equipment and systems are not accessible, blocked or damaged (ie; fire pull station, fire hose, panel, gas feed, water shut off, blocked breakers) | B | Principal | 09/11/23 | Details |
09/06/23 | Fan room 8 | guarding or shielding not in place | A | Caretaker | 09/18/23 | Details |
09/06/23 | fan room 9 | guarding or shielding not in place | A | Caretaker | 09/18/23 | Details |
09/06/23 | mechanical room | improper storage of flammable/combustible material | B | Caretaker | 09/18/23 | Details |
09/06/23 | 301 | fire exit route sign (yellow TDSB) - not posted / requires updating | B | Caretaker | 09/18/23 | Details |
09/06/23 | 302 | fume hood - improper use (not to be used for storage) | B | Caretaker | 09/18/23 | Details |
09/06/23 | 302 | fume hood - there is no power to the fume hood in the chemical prep room | A | Caretaker | 09/18/23 | Details |
09/06/23 | 302A | panel (specify) | A | Caretaker | 09/18/23 | Details |
09/06/23 | 302A | PPE - personal protective equipment not available | B | Principal | 09/11/23 | Details |
09/06/23 | 302A | broken glass container is required in science storage/prep room | B | Principal | 09/11/23 | Details |
09/06/23 | 302A | fume hood - there is no power to the fume hood in the chemical prep room | A | Caretaker | 09/18/23 | Details |
09/06/23 | 302A | spill kit or bucket of sand is not available | B | Principal | 09/11/23 | Details |
09/06/23 | 306 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Caretaker | 09/18/23 | Details |
09/06/23 | 304a | receptacle/light switch (specify) | A | Caretaker | 09/18/23 | Details |
09/06/23 | 304a | exhaust - exhaust required repair | A | Caretaker | 09/18/23 | Details |
09/06/23 | 306 | combustible material being displayed that is not fire rated/treated | A | Caretaker | 09/18/23 | Details |
09/06/23 | mechanical room | guarding or shielding not in place | A | Caretaker | 09/18/23 | Details |
09/06/23 | mechanical room | guarding or shielding not in place | A | Caretaker | 09/18/23 | Details |
09/06/23 | mechanical room | guarding or shielding not in place | A | Caretaker | 09/18/23 | Details |
09/06/23 | mechanical room | ladder not to standard (specify) | A | Caretaker | 09/18/23 | Details |
10/04/23 | staff lounge | microwave stickers missing | B | Principal | 11/03/23 | Details |
10/04/23 | staff lounge | Joint Health & Safety Committee meeting minutes not posted (including names and contact numbers) | B | Principal | 11/03/23 | Details |
10/04/23 | staff lounge | Workplace Inspection Form | B | Principal | 11/06/23 | Details |
10/04/23 | 304 | eyewash station required or in need of repair (specify) | A | Caretaker | 10/31/23 | Details |
10/04/23 | 301 | improper storage of flammable/combustible material | B | Principal | 11/06/23 | Details |
11/15/23 | Caretakers lunch room | eyewash station required or in need of repair (specify) | A | Caretaker | 11/29/23 | Details |
12/12/23 | Pool Filter Room | extinguisher - tag missing or annual inspection more than 3 months overdue | A | Caretaker | 01/11/24 | Details |
12/12/23 | Pool Filter Room | extinguisher - tag missing or annual inspection more than 3 months overdue | A | Caretaker | 01/11/24 | Details |
12/12/23 | Pool Filter Room | insufficient means of communication (ie: PA, radio, etc.) | B | Caretaker | 01/10/24 | Details |
12/12/23 | Boys Change Room | paint flaking, chipping, possible lead exposure | A | Caretaker | 01/10/24 | Details |
12/12/23 | Boys Change Room | leaking/pooling/ponding of water or liquid (be as specific as possible) | A | Caretaker | 01/10/24 | Details |
12/12/23 | Boys Change Room | ceiling tiles missing/loose | A | Caretaker | 01/10/24 | Details |
12/12/23 | electrical room | ceiling tiles missing/loose | A | Caretaker | 01/10/24 | Details |
12/12/23 | projection booth | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 01/10/24 | Details |
12/12/23 | Fan rooms | ceiling damaged (specify) | A | Caretaker | 01/10/24 | Details |
12/12/23 | mechanical room | guarding or shielding not in place | A | Caretaker | 01/10/24 | Details |
12/12/23 | Pool Filter Room | workplace inspection hazards (E-WIP) not addressed | B | Caretaker | 01/11/24 | Details |
12/12/23 | Girls Change Room | paint flaking, chipping, possible lead exposure | A | Caretaker | 01/10/24 | Details |
12/12/23 | Fan room 8 | guarding or shielding not in place | A | Caretaker | 01/10/24 | Details |
12/12/23 | fan room 1st floor, unlabelled red doors | handrail not secure, damaged or required | A | Caretaker | 01/10/24 | Details |
12/12/23 | Hall | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 01/10/24 | Details |
12/12/23 | fan room 1st floor, unlabelled red doors | extinguisher - tag missing or annual inspection more than 3 months overdue | A | Caretaker | 01/10/24 | Details |
12/12/23 | Storage | ceiling tiles missing/loose | A | Caretaker | 01/10/24 | Details |
01/16/24 | 108 | ceiling tiles missing/loose | A | Caretaker | 01/25/24 | Details |
01/16/24 | Fan Room 5 | extinguisher - tag missing or annual inspection more than 3 months overdue | A | Caretaker | 01/25/24 | Details |
01/16/24 | Boy's Washroom | unable to inspect (specify why if possible) | B | Caretaker | 01/25/24 | Details |
01/16/24 | Girl's Washroom | unable to inspect (specify why if possible) | B | Caretaker | 01/25/24 | Details |
02/01/24 | fan room 10 | eyewash station required or in need of repair (specify) | A | Caretaker | 02/07/24 | Details |
02/01/24 | 302A | eyewash station required or in need of repair (specify) | A | Caretaker | 02/07/24 | Details |
02/01/24 | 302A | carts for transporting chemicals do not have 4 sides | B | Principal | 03/01/24 | Details |
02/01/24 | 302A | inspections not up to date (specify equipment) | B | Principal | 03/01/24 | Details |
02/01/24 | 302A | fume hood - improper use (not to be used for storage) | B | Principal | 03/01/24 | Details |
02/01/24 | fan room 1 | guarding or shielding not in place | A | Caretaker | 02/07/24 | Details |
02/01/24 | Fan Room 3 | guarding or shielding not in place | A | Caretaker | 02/07/24 | Details |
02/01/24 | Fan Room 6 | ceiling damaged (specify) | A | Caretaker | 02/07/24 | Details |
02/01/24 | 119c | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Principal | 03/01/24 | Details |
02/01/24 | 121 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Principal | 03/01/24 | Details |
02/01/24 | fan room 9 | guarding or shielding not in place | A | Caretaker | 02/07/24 | Details |
02/01/24 | Pool Filter Room | insufficient means of communication (ie: PA, radio, etc.) | B | Principal | 03/01/24 | Details |
02/01/24 | 121 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Principal | 03/01/24 | Details |
02/01/24 | Mens staff Washroom | ceiling tiles missing/loose | A | Caretaker | 02/07/24 | Details |
02/01/24 | Fan room 8 | guarding or shielding not in place | A | Caretaker | 02/07/24 | Details |
02/01/24 | 119 | equipment damaged or improperly stored (specify) | B | Principal | 03/01/24 | Details |
02/01/24 | 123 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | Principal | 03/01/24 | Details |
02/29/24 | 206 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Principal | 05/03/24 | Details |
02/29/24 | 104 | window covering damaged/in need of repair | A | Caretaker | 04/02/24 | Details |
02/29/24 | Cafetorium | microwave stickers missing | B | Principal | 05/03/24 | Details |
04/24/24 | 3rd By fan #10 | panel (specify) | A | Caretaker | 05/04/24 | Details |
04/24/24 | fan room 2 | exposed wiring/damaged cord/ground pin missing | A | Caretaker | 05/04/24 | Details |
04/24/24 | 111 | exposed wiring/damaged cord/ground pin missing | A | Caretaker | 05/04/24 | Details |
04/24/24 | 117 | exposed wiring/damaged cord/ground pin missing | A | Caretaker | 05/04/24 | Details |
04/26/24 | 111 | ceiling tiles missing/loose | A | Caretaker | 05/04/24 | Details |
04/26/24 | 115 | lighting in need of repair (maintenance issue) | A | Caretaker | 05/04/24 | Details |
04/26/24 | 115A | microwave stickers missing | B | Principal | 05/03/24 | Details |
04/26/24 | Cafetorium | microwave stickers missing | B | Principal | 05/03/24 | Details |
05/06/24 | 201 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Principal | 06/17/24 | Details |
05/06/24 | 203 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | Principal | 06/17/24 | Details |
05/06/24 | 205a | ceiling tiles missing/loose | A | | | Details |
05/06/24 | 210a | microwave stickers missing | B | Principal | 06/17/24 | Details |
05/06/24 | 214 | window covering recommended on 1st floor (emergency lockdown procedures) | B | Principal | 06/17/24 | Details |
05/06/24 | 202a | microwave stickers missing | B | Principal | 06/17/24 | Details |
06/19/24 | 104 | fire exit route sign (yellow TDSB) - not posted / requires updating | B | Principal | 06/21/24 | Details |
06/19/24 | 103 Drama Complex | fire exit route sign (yellow TDSB) - not posted / requires updating | B | Principal | 06/21/24 | Details |
06/19/24 | Computer Lab | fire exit route sign (yellow TDSB) - not posted / requires updating | B | Principal | 06/21/24 | Details |
06/19/24 | Cafetorium | fire exit route sign (yellow TDSB) - not posted / requires updating | B | Principal | 06/21/24 | Details |
06/19/24 | Pool Filter Room | unable to inspect (specify why if possible) | B | | | Details |
06/19/24 | Fan room 8 | guarding or shielding not in place | A | | | Details |