Health and Safety (H&S) workplace inspections are conducted every month in all of our 582 operating schools. Below you can find the H&S reports for your school, for the 2021-2022 school years.  More information and Frequently Asked Questions

Date InspectedLocation in SchoolHealth & Safety Issue ObservedClassAction Taken ByDate Action TakenDetails
09/26/23Boiler Room - 163emergency lighting damaged/missing ACaretaker11/23/23Details
09/26/23117 - Autoeyewash station required or in need of repair (specify)ACaretaker11/23/23Details
09/27/23135paint flaking, chipping, possible lead exposureACaretaker11/23/23Details
09/27/23137ceiling damaged (specify)ACaretaker11/23/23Details
09/27/23204A - Chem. Prep. Roominspections not up to date (specify equipment)BCaretaker11/23/23Details
09/27/23135air - return/supply (specify)ACaretaker11/23/23Details
09/27/23204A - Chem. Prep. Roomfume hood - there is no power to the fume hood in the chemical prep roomACaretaker11/23/23Details
09/27/23Boiler Room - 138door/access door (specify)ACaretaker11/23/23Details
10/16/23137Aceiling tiles missing/looseACaretaker11/23/23Details
11/28/23117 - Autoceiling tiles missing/looseACaretaker04/20/24Details
11/28/23117 - Autoinspections not up to date (specify equipment)BCaretaker03/18/24Details
11/28/23192temperature does not meet TDSB GuidelineACaretaker03/18/24Details
11/28/23Exit 9paint flaking, chipping, possible lead exposureACaretaker04/20/24Details
11/28/23Exit 9ceiling damaged (specify)ACaretaker04/20/24Details
11/28/23Courtyardexposed wiring/damaged cord/ground pin missingACaretaker04/20/24Details
11/28/23Courtyardwindow damaged, in need of repair (specify)ACaretaker04/20/24Details
11/28/23Office - Mainlighting in need of repair (maintenance issue)ACaretaker04/20/24Details
11/28/23Office - Mainceiling damaged (specify)ACaretaker04/20/24Details
11/28/23Hallwayceiling damaged (specify)ACaretaker03/18/24Details
11/28/23142paint flaking, chipping, possible lead exposureACaretaker04/20/24Details
11/28/23142ceiling damaged (specify)ACaretaker04/20/24Details
11/28/23143paint flaking, chipping, possible lead exposureACaretaker04/20/24Details
11/28/23143ceiling tiles missing/looseACaretaker04/20/24Details
11/28/23117 - Autopaint flaking, chipping, possible lead exposureACaretaker04/20/24Details
12/04/23132microwave stickers missingBCaretaker03/18/24Details
12/04/23Library staff work roommicrowave stickers missingBCaretaker03/18/24Details
12/04/23Guidance Room 7microwave stickers missingBCaretaker03/18/24Details
01/02/24202equipment damaged or improperly stored (specify)BCaretaker10/02/24Details
01/02/24202inappropriate storage of materials/furniture/shelving, or clutterBCaretaker10/02/24Details
01/02/24207combustible material being displayed that is not fire rated/treatedA  Details
01/02/24201extension cord/power bar - inappropriate use of extension cord/power bar (be specific)BCaretaker10/02/24Details
01/02/24140 - Wood Shopanti-slip strips missingBCaretaker06/03/24Details
01/02/24141 - Robioticsemergency exit sign (specify)ACaretaker Details
01/02/24141 - Robioticseyewash station required or in need of repair (specify)A  Details
01/02/24141 - Robioticsceiling damaged (specify)ACaretaker10/02/24Details
01/02/24141 - Robioticscombustible material being displayed that is not fire rated/treatedACaretaker10/02/24Details
01/02/24214combustible material being displayed that is not fire rated/treatedA  Details
01/02/24212combustible material being displayed that is not fire rated/treatedA  Details
01/02/24213combustible material being displayed that is not fire rated/treatedA  Details
01/02/24211combustible material being displayed that is not fire rated/treatedA  Details
01/02/24210combustible material being displayed that is not fire rated/treatedA  Details
01/02/24209combustible material being displayed that is not fire rated/treatedA  Details
01/02/24208combustible material being displayed that is not fire rated/treatedA  Details
01/02/24140 - Wood Shopcombustible material being displayed that is not fire rated/treatedACaretaker06/03/24Details
01/02/24205combustible material being displayed that is not fire rated/treatedA  Details
01/02/24205combustible material being displayed that is not fire rated/treatedA  Details
01/02/24204combustible material being displayed that is not fire rated/treatedACaretaker10/02/24Details
01/02/24202combustible material being displayed that is not fire rated/treatedACaretaker10/02/24Details
01/02/24201combustible material being displayed that is not fire rated/treatedACaretaker10/02/24Details
01/02/24229combustible material being displayed that is not fire rated/treatedA  Details
01/02/24221combustible material being displayed that is not fire rated/treatedA  Details
01/02/24227combustible material being displayed that is not fire rated/treatedA  Details
01/02/24225combustible material being displayed that is not fire rated/treatedA  Details
01/02/24232combustible material being displayed that is not fire rated/treatedA  Details
01/02/24214extension cord/power bar - inappropriate use of extension cord/power bar (be specific)B  Details
01/02/24209extension cord/power bar - inappropriate use of extension cord/power bar (be specific)B  Details
01/02/24206extension cord/power bar - inappropriate use of extension cord/power bar (be specific)B  Details
01/02/24225extension cord/power bar - inappropriate use of extension cord/power bar (be specific)B  Details
01/02/24221extension cord/power bar - inappropriate use of extension cord/power bar (be specific)B  Details
01/02/24210trip hazard (i.e. flooring, other materials)A  Details
01/02/24207fire exit route sign (yellow TDSB) - not posted / requires updatingB  Details
01/02/24205eyewash station required or in need of repair (specify)A  Details
01/02/24204A - Chem. Prep. Roombroken glass container is required in science storage/prep roomBCaretaker10/02/24Details
01/02/24204ceiling tiles missing/looseA  Details
01/02/24202fire exit route sign (yellow TDSB) - not posted / requires updatingBCaretaker10/02/24Details
02/12/24222fire exit route sign (yellow TDSB) - not posted / requires updatingBCaretaker03/18/24Details
02/12/24117 - Autodamaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACaretaker03/18/24Details
02/12/24218eyewash station required or in need of repair (specify)ACaretaker03/18/24Details
03/14/24204A - Chem. Prep. Roomunable to inspect (specify why if possible)BCaretaker04/20/24Details
03/14/24208A - Chem. Storage Roomextinguisher - tag missing or annual inspection more than 3 months overdueACaretaker03/18/24Details
03/14/24137ceiling damaged (specify)ACaretaker04/20/24Details
03/14/24137trip hazard (i.e. flooring, other materials)ACaretaker04/20/24Details
03/14/24Girl's Change roompaint flaking, chipping, possible lead exposureACaretaker04/20/24Details
03/14/24Electrical Room - 163Adrain (specify)ACaretaker04/20/24Details
03/14/24117 - Autotrip hazard (i.e. flooring, other materials)ACaretaker04/20/24Details
03/14/24117 - Automicrowave stickers missingBCaretaker04/20/24Details
03/14/24Boiler Room - 163unable to inspect (specify why if possible)BCaretaker04/20/24Details
04/23/24Boiler Room - 163guarding or shielding not in placeACaretaker06/03/24Details
04/23/24Staff Roomlighting in need of repair (maintenance issue)ACaretaker06/03/24Details
04/23/24Serverylighting in need of repair (maintenance issue)ACaretaker06/03/24Details
04/23/24165D - Dressing Roomceiling damaged (specify)ACaretaker06/03/24Details
04/23/24Cafeteria damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACaretaker06/03/24Details
04/23/24Exit 5evidence of pests (interior or exterior), be as specific as possible.ACaretaker06/03/24Details
04/23/24Fan Room 2 - in Cafe storage roomlighting in need of repair (maintenance issue)ACaretaker06/03/24Details
04/23/24Exit 4damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACaretaker06/03/24Details
04/23/24Hallwaydamaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs)ACaretaker06/03/24Details
04/23/24Hallwayceiling damaged (specify)ACaretaker06/03/24Details
05/16/24Staff RoomPO34 TDSB Harassment PolicyBCaretaker06/03/24Details
05/16/24117 - Autotrip hazard (i.e. flooring, other materials)ACaretaker06/03/24Details
05/16/24117 - Autoinspections not up to date (specify equipment)BCaretaker06/03/24Details
05/16/24142ceiling damaged (specify)ACaretaker06/03/24Details
05/16/24Computer Roomunable to inspect (specify why if possible)BCaretaker06/03/24Details
05/16/24Boiler Room - 138eyewash station required or in need of repair (specify)ACaretaker06/03/24Details
05/16/24Mechanical Rooms 1st floorunable to inspect (specify why if possible)BCaretaker06/03/24Details
05/16/24Stageinspections not up to date (specify equipment)BCaretaker06/03/24Details
05/16/24Boiler Room - 138egress blocked or insufficient path (doorway, hallway or stairwell)BCaretaker06/03/24Details
06/03/24114display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls)B  Details
06/03/24112display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls)B  Details
06/03/24110display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls)B  Details
06/03/24107eyewash station required or in need of repair (specify)A  Details
06/03/24141 - Robioticsceiling tiles missing/looseA  Details
06/03/24140 - Wood Shopdoor/access door (specify)A  Details
06/03/24141 - Robioticsdisplay(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls)B  Details
06/03/24140 - Wood Shopdisplay(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls)B  Details
06/03/24204A - Chem. Prep. Roombroken glass container is required in science storage/prep roomB  Details
06/03/24218A - Chem. Prep. Roombroken glass container is required in science storage/prep roomB  Details
06/03/24123display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls)B  Details
06/03/24123extension cord/power bar - inappropriate use of extension cord/power bar (be specific)B  Details
06/03/24119display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls)B  Details
06/03/24107display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls)B  Details